Electrical Work
I have an older home that needs some electrical updates:
1. Main panel:
The meter socket has been pulled loose from the house and needs to be secured. Panel has a main breaker, and all breakers are sized correctly. There are copper conductors for the main and all branch circuits. The neutral conductors need to be terminated individually on the neutral bar. There is no grounding conductor present. Would recommend having the service grounded. The conduit running along the back from the panel needs to be strapped back in place. The a/c disconnect has an oversized breaker and needs to be changed.
2. Receptacles and switches:
All outlets are 2 wire non grounded. The kitchen, bathrooms, garage, and outdoor outlets need to be replaced with GFCI outlets and weather proof covers for the on...